Cross-section calculation
Date: 18/11/2026 · goksankablo.az · calculator · +994 55 903 85 85Engineering tool
Cross-section calculator
Find the smallest suitable cross-section per IEC 60364-5-52 by current-carrying capacity, voltage drop and breaker coordination, then add the matching cable to the cart or quote.
Recommended cross-section
Copper (Cu) · PVC · 3-phase, 400 V · method C
- Current-carrying capacity Iz′ 76,00 A ≥ Ib 63,00 A
- Voltage drop 10,13 V = 2,53 % ≤ 5,0 %
- Breaker In 63 A: Ib ≤ In ≤ Iz′
Why this cross-section? Cross-section chosen by current-carrying capacity
| Section, mm² | Iz, A | Iz′, A | ΔU, V | ΔU, % | Result |
|---|---|---|---|---|---|
| 1,5 | 17.5 | 17,50 | 108,04 | 27,01 | Current too high |
| 2,5 | 24 | 24,00 | 64,83 | 16,21 | Current too high |
| 4 | 32 | 32,00 | 40,52 | 10,13 | Current too high |
| 6 | 41 | 41,00 | 27,01 | 6,75 | Current too high |
| 10 | 57 | 57,00 | 16,21 | 4,05 | Current too high |
| 16 · recommended | 76 | 76,00 | 10,13 | 2,53 | OK |
| 25 | 96 | 96,00 | 6,79 | 1,70 | OK |
| 35 | 119 | 119,00 | 4,93 | 1,23 | OK |
| 50 | 144 | 144,00 | 3,55 | 0,89 | OK |
| 70 | 184 | 184,00 | 2,62 | 0,65 | OK |
| 95 | 223 | 223,00 | 2,01 | 0,50 | OK |
| 120 | 259 | 259,00 | 1,65 | 0,41 | OK |
| 150 | 299 | 299,00 | 1,38 | 0,35 | OK |
| 185 | 341 | 341,00 | 1,18 | 0,30 | OK |
| 240 | 403 | 403,00 | 0,98 | 0,24 | OK |
| 300 | 464 | 464,00 | 0,84 | 0,21 | OK |
Indicative engineering calculation (IEC 60364-5-52:2009, Annex B and G). Consult the project engineer for the final choice.